 R
Digital Temperature Controllers
Compact, Intelligent Temperature Controllers H 1/32 DIN sized controller saves panel
space, measures just 100 mm deep
E5GN
H Accepts thermocouple, platinum RTD,
non-contact temperature sensor, and analog temperature inputs
H Auto-tuning and self-tuning available;
functions can be used simultaneously
H Heating or heating/cooling control H Water-resistant construction (NEMA 4X,
equivalent to IP66)
H Conforms to UL, CSA, and IEC safety
standards as well as CE marking
uC
H 3-year warranty
Ordering Information
Optional communications and event input boards are shown on the following page.
J STANDARD TEMPERATURE CONTROLLERS
Size Power supply voltage 100 to 240 VAC Alarm points Output Part number Thermocouple input --- 1 (See Note 1) 24 V AC/DC --- 1 (See Note 1) Relay Voltage (for driving SSR) Relay Voltage (for driving SSR) Relay Voltage (for driving SSR) Relay Voltage (for driving SSR) E5GN-RTC AC100-240 E5GN-QTC AC100-240 E5GN-R1TC AC100-240 E5GN-Q1TC AC100-240 E5GN-RTC AC/DC24 E5GN-QTC AC/DC24 E5GN-R1TC AC/DC24 E5GN-Q1TC AC/DC24 Platinum RTD input E5GN-RP AC100-240 E5GN-QP AC100-240 E5GN-R1P AC100-240 E5GN-Q1P AC100-240 E5GN-RP AC/DC24 E5GN-QP AC/DC24 E5GN-R1P AC/DC24 E5GN-Q1P AC/DC24
1/32 DIN 48(W) x 24 (H) x 100(D) mm
Note: 1. If the heating/cooling function is used, ALM1 will be used for control output; the alarm output will not be available. 2. Control output 2 for heating/cooling control is a relay output
J TEMPERATURE CONTROLLERS WITH COMMUNICATIONS
Size Power supply voltage 100 to 240 VAC 24 V AC/DC Communication Output type RS-485 Relay Voltage (for driving SSR) Relay Voltage (for driving SSR) Part number Thermocouple input E5GN-R03TC-FLK AC100-240 E5GN-Q03TC-FLK AC100-240 E5GN-R03TC-FLK AC/DC24 E5GN-Q03TC-FLK AC/DC24 Platinum RTD input E5GN-R03P-FLK AC100-240 E5GN-Q03P-FLK AC100-240 E5GN-R03P-FLK AC/DC24 E5GN-Q03P-FLK AC/DC24
1/32 DIN 48(W) x 24 (H) x 100(D) mm
67
E5GN
J INPUT RANGES
Input type Name 1800 1700 1600 1500 1400 1300 1200 1100 1000 900 800 700 600 500 400 300 200 100 0 -100 -200 Platinum resistance thermometer Pt100 JPt100
E5GN
Note: Lightly shaded ranges indicate default settings.
850
500.0
500.0
100.0 0.0 -200 -199.9 -199.9
100.0 0.0
Set value
0
1
2
3
4
Input type Name 1800 1700 1600 1500 1400 1300 1200 1100 1000 900 800 700 600 500 400 300 200 100 0 -100 -200 K J T
Thermocouple E L U N R
1700
ES1A Non-contact Temperature Sensor S
1700
Analog input 0 to 50 mV Usable in the following ranges by scaling: -1999 to 9999 or -199.9 to 999.9
B
1800
K10 to 70C
K60 to 120C
K115 to K160 to 165C 260C
1300
1300
850
850
600 500.0 400.0 400 400.0 400 400.0 260 120 70 100 -20.0 -100 -200 -200 -199.9 -20.0 0 -100 -200 -199.9 -200 0 0 0 0 0 0 165
Set value
0
1
2
3
4
17
5
6
7
18
8
9
10
11
12
13
14
15
16
Applicable standards by input type are as follows: K, J, T, E, N, R, S, B: JIS C1602-1995 L: Fe-CuNi, DIN 43710-1985 U: Cu-CuNi, DIN 43710-1985 JPt100: JIS C1604-1989, JIS C1606-1989 Pt100: JIS C1604-1997, IEC751
68
E5GN
E5GN
Specifications
J RATINGS
Supply voltage Operating voltage range Power consumption Sensor input 100 to 240 VAC, 50/60 Hz 85% to 110% of rated supply voltage 7 VA 4 VA/2.5 W Thermocouple: K, J, T, E, L, U, N, R, S, B Platinum resistance thermometer: Pt100, JPt100 Non-contact temperature sensor: 10 to 70_C, 60 to 120_C, 115 to 165_C, 160 to 260_C Voltage input: 0 to 50 mV Relay output Voltage output Alarm output Control method Setting method Indication method Ambient operating temperature Storage temperature Ambient humidity SPST-NO, 250 VAC, 2 A (resistive load), electrical life: 100,000 operations 12 VDC +15%/-20% (PNP), max. load current: 21 mA, with short-circuit protection circuit SPST-NO, 250 VAC, 1 A (resistive load), electrical life: 100,000 operations PID or ON/OFF control Digital setting using front panel keys 7-segment digital display and single-lighting indicator Character height: PV: 7.0 mm; SV: 3.5 mm -10 to 55_C (14F to 131F) with no condensation or icing _C -25 to 65_C (-13F to 149F) with no condensation or icing _C 25% to 85% RH 24 VAC, 50/60 Hz/24 VDC
Control output
J CHARACTERISTICS
Indication accuracy Thermocouple: 0.5% of indicated value or 1_C, whichever greater, 1 digit max. (See Note) Platinum resistance thermometer: 0.5% of indicated value or 1_C, whichever greater, 1 digit max. Analog input: 0.5% FS1 digit max. CT input: 5% FS1 digit max. 0.1 to 999.9 EU (in units of 0.1 EU) 0.1 to 999.9 EU (in units of 0.1 EU) 0 to 3999 s (in units of 1 s) 0 to 3999 s (in units of 1 s) 1 to 99 s (in units of 1 s) 0.0% to 100.0% (in units of 0.1%) -1999 to 9999 (decimal point position depends on input type) 500 ms 20 M min. at 500 VDC 2000 VAC, 50 or 60 Hz for 1 min between different charging terminals 10 to 55 Hz, 10 m/s2 for 2 hours each in X, Y and Z directions 300 m/s2, 3 times each in 3 axes, 6 directions (relay: 100 m/s2) Approx. 90 g; mounting bracket: Approx. 10 g Front panel: NEMA4X for indoor use (equivalent to IP66), rear case: IP20, terminals: IP00 EEPROM non-volatile memory (number of writes: 100,000)
Hysteresis Proportional band (P) Integral time (I) Derivative time (D) Control period Manual reset value Alarm setting range Sampling period Insulation resistance Dielectric strength Vibration resistance Shock resistance Weight Protective structure Memory protection Note:
The indication of K thermocouples in the -200 to 1300C range, and T and N thermocouples at a temperature of -100C or less, and U and L thermocouples at any temperature is 2C1 digit maximum. The indication of B thermocouples at a temperature of 400C or less is unrestricted. The indication of R and S thermocouples at a temperature of 200C or less is 3C1 digit maximum.
(This table continues on the next page.)
69
E5GN
Specifications Table - continued from previous page
EMC Emission Enclosure: Emission AC Mains: Immunity ESD: Immunity RF-interference: Immunity Conducted Disturbance: Immunity Burst: Approved standards EN55011 Group 1 class A EN55011 Group 1 class A EN61000-4-2: 4 kV contact discharge (level 2) 8 kV air discharge (level 3) ENV50140: 10 V/m (amplitude modulated, 80 MHz to 1 GHz) (level 3) 10 V/m (pulse modulated, 900 MHz) ENV50141: 10 V (0.15 to 80 MHz) (level 3) EN61000-4-4: 2 kV power-line (level 3) 2 kV I/O signal-line (level 4)
E5GN
UL3121-1, CSA22.2 No. 14, E.B.1402C Conforms to EN50081-2, EN50082-2, EN61010-1 (IEC61010-1)
J COMMUNICATIONS SPECIFICATIONS
Transmission path connection Communications method (See Note) Synchronization method Baud rate Transmission code Data bit length (See Note) Stop bit length (See Note) Error detection Multiple points RS-485 (two-wire, half duplex) Start-stop synchronization 1,200/2,400/4,800/9,600/19,200 bps ASCII 7 or 8 bits 1 or 2 bits Vertical parity (none, even, odd) Frame check sequence (FCS): with SYSMAC WAY Block check character (BCC): with CompoWay/F Not available RS-485 Not available 40 bytes
Flow control Interface (See Note) Retry function Communications buffer
Note: The baud rate, data bit length, stop bit length, or vertical parity can be individually set using the communications setting level.
Nomenclature
Temperature unit No.1 display
CMW
STP
OUT
Operation indicators
No.2 display
Level key
Up key
Mode key
Down key
70
E5GN
E5GN
Dimensions
Unit: mm (inch)
48 (1.89) 3 (0.12) 100 (3.94)
35 (1.38) 24 (0.94)
36.8 (1.45)
22 (0.87)
44.8 (1.76)
22 (0.87)
* When carrying out maintenance on the E5GN, only the terminal plate can be drawn out with the terminal leads still attached.
Panel Cutout
Mounted Separately Group Mounted 48 number of units - 2.5 0 (1.89 number of units - 0.10) 60 (2.36) min.
+0.3 +1.0
22 0 (0.87)
60 (2.36) min.
45 0 (1.77)
+0.6
Mounting separately does not allow waterproofing.
*
22 0 (0.87)
+0.3
Insert the Controller through the hole in the panel from the front and push the adapter on from the rear. Push the adapter up to the back of the panel ensuring that the controller is pushed all the way in, removing any gap between the Controller, panel, and adapter. Finally, use the two screws on the adapter to secure the unit in place. To mount the E5GN so that it is waterproof, insert the waterproof packing onto the E5GN. When two or more E5GN Controllers are mounted, make sure that the surrounding temperature does not exceed the allowable operating temperature ranges in the specifications.
* *
71
E5GN
E5GN
Wiring Terminals
*
The voltage output (control output) is not electrically insulated from the internal circuits. When using a grounding thermocouple, do not connect the control output terminals to the ground. If the control output terminals are connected to the ground, errors will occur in the measured temperature values as a result of leakage current.
Control output Relay output
*
Standard insulation is applied to the power supply I/O sections. If reinforced insulation is required, connect the input and output terminals to a device without any exposed current-carrying parts or to a device with standard insulation suitable for the maximum operating voltage of the power supply I/O section.
Voltage output
Alarm output
Two input power supplies are available: 100 to 240 VAC or 24 VAC/VDC (no polarity).
Input power supply
Analog input
R
OMRON ELECTRONICS, INC.
One East Commerce Drive Schaumburg, IL 60173
OMRON CANADA, INC.
885 Milner Avenue Scarborough, Ontario M1B 5V8
1-800-55-OMRON
Cat. No. GCTC13 8/00 Specifications subject to change without notice.
416-286-6465
Printed in U.S.A.


▲Up To Search▲   

 
Price & Availability of E5GN-Q1PACDC24

All Rights Reserved © IC-ON-LINE 2003 - 2022  

[Add Bookmark] [Contact Us] [Link exchange] [Privacy policy]
Mirror Sites :  [www.datasheet.hk]   [www.maxim4u.com]  [www.ic-on-line.cn] [www.ic-on-line.com] [www.ic-on-line.net] [www.alldatasheet.com.cn] [www.gdcy.com]  [www.gdcy.net]


 . . . . .
  We use cookies to deliver the best possible web experience and assist with our advertising efforts. By continuing to use this site, you consent to the use of cookies. For more information on cookies, please take a look at our Privacy Policy. X